4801-0102 REV 9/96 ICSICS--500 Environmental Controller500 Environmental Controller With Back-up system and Contactor Panel Hired Hand, Inc. 1733
Integrated Control System 500 8 6.1.2.2.4.Five/Ten Minute Timer INSTALL JUMPER FOR5 MINUTE TIMER The controller's internal timer is normally a
Integrated Control System 500 9 6.1.2.2.7.Variable Speed Fan (Enhanced Version Only) 6.1.2.2.7.1.Variable Minimum Adjust If you have the enhanced v
Integrated Control System 500 10 the fan will be running at minimum speed when temperature equals 70 degrees. Example: Minimum 40 percent Offset
Integrated Control System 500 11
Integrated Control System 500 12
Integrated Control System 500 13
Integrated Control System 500 14 Black White White Black Red AC Supply Control CircuitWhiteYellowOrangeRedBrownBlueBlackGreenWhi
Integrated Control System 500 15 the sensor reaches one degree above the high limit, the back-up board would start all stages set to cool one. (This
Integrated Control System 500 16
Integrated Control System 500 17 6.3. Contactor Panel 6.3.1. General Description Hired Hand’s Contactor Control System is a pre-wired set of heavy c
Integrated Control System 500 Table of Contents Integrated Control System - 500 Table of Contents 1. Purpose ________________________________________
Integrated Control System 500 18 7. Operation 7.1. Curtain Operation 7.1.1. Standard If the controller sees that temperature inside the house is abov
Integrated Control System 500 19 7.2. Stage Operation Stages may be operated by the controller automatically, by the controller on the timer, or manu
Integrated Control System 500 20 80 + 5 + 2 = 87 If the Target Temp is set at 80 degrees, Offset set at 5 degrees, and Differential set at 2 deg
Integrated Control System 500 21
Integrated Control System 500 22
Integrated Control System 500 23
Integrated Control System 500 24 10. Troubleshooting Warning! WARNING! Electric Shock Hazard. These tests must only be run by a Qualified Technici
Integrated Control System 500 25 19. Check to see if you can turn the stages on and off with the toggle switches on the front of the contactor panel.
Integrated Control System 500 26 Temperature Vs. Resistance for Hired-Hand Temperature Sensors. Resistance (Kohms) Temp (F) Temp (C) Resistance (K
Integrated Control System 500 27 Resistance (Kohms) Temp (F) Temp (C) Resistance (Kohms) Temp (F) Temp (C) 19.065 51.6 10.9 9.956 77.2 25.1
Integrated Control System 500 1 Integrated Control System - 500 1. Purpose The Integrated Control System model 500 (ICS-500) is an eight stage temper
Integrated Control System 500 28 Resistance (K ohms) Temp (F) Temp (C) Resistance (Kohms) Temp (F) Temp (C) 5.326 104.0 40.0 4.454 112.1 44.
Integrated Control System 500 29
Integrated Control System 500 30
Integrated Control System 500 31 Part No. Description 1018-0104 STND_OFF LCBSB-10-01A-RT 1018-2059 STND_OFF SCBS-8N 1039-2031 KNOB 1" dia 1
Integrated Control System 500 32 Chart E Part No. Description 6404-1174 /PCB111 after QA 6404-1185 /PCB115 after QA Chart F Part No. Descriptio
Integrated Control System 500 2 4. Warranty One Year Limited Warranty The ICS-500 is warranted for one year from date of purchase against electrica
Integrated Control System 500 3 CONTROLLERSystem 500POWER CURTAINPOWER CURTAINAutomaticmode...!!Back-UpSystemManual StageControlsSystem 500Power Curt
Integrated Control System 500 4 6.1.2. Controls 6.1.2.1. Front Panel The following controls are located on the outside of the panel. 6.1.2.1.1.Autom
Integrated Control System 500 5 6.1.2.1.3.Alternate Program Switch PROGRAM(Programa)AB Each of the 256 stage programs has another “shadow” program.
Integrated Control System 500 6 6.1.2.1.6.OSC High Limit (Enhanced Version Only) OUTSIDE SENSOR CONTROLOSCINCREASEDECREASE(Disminuir) (Aumentar) Th
Integrated Control System 500 7 6.1.2.2.2.Stage On Timer Jumpers Stage 1Stage 2Stage 3Stage 4Stage 5Stage 6Stage 7Stage 8Jumper pins